EvaluateEfficiency by Equipment Type6 min readUpdated

Key takeaways

  • Packaged units cool 55% of air-conditioned commercial buildings, and 66% in hot climates (EIA CBECS 2018).
  • Field studies found economizer failure rates of 64% to 80% and frequent charge and airflow problems.
  • Measure temperature split, superheat/subcooling, airflow and amps; trend run hours against weather.
  • Fix economizers, airflow, charge and coils before considering a refrigerant-side treatment.
  • RTU fleets allow treated-versus-untreated comparisons, which make results easier to verify.

Packaged rooftop units (RTUs) are the workhorses of American commercial buildings. The U.S. Energy Information Administration's 2018 Commercial Buildings Energy Consumption Survey found that 55% of commercial buildings with cooling use packaged air-conditioning units, and 66% in hot or very hot climate zones, making them the most common cooling equipment in every climate zone (EIA). They are also among the least watched. A building may have twenty RTUs, each serviced twice a year by a technician who changes filters and belts, while nobody tracks how efficiently any of them actually runs. This page explains how RTUs lose efficiency, how to find the losses, and where an internal oil-film treatment fits.

How a rooftop unit works

An RTU puts the whole air-conditioning system in one cabinet: compressor(s), an outdoor condenser coil with fans, an indoor evaporator coil, a supply fan, filters, and usually a heating section (gas furnace, electric heat, or a heat pump circuit). Most also have an economizer, a set of motorized dampers that bring in cool outdoor air for "free cooling" when conditions allow, and a minimum outdoor-air position for ventilation. The unit connects to ductwork through the roof curb.

RTUs serve retail, office, school, restaurant and light industrial buildings, and most are small: in the California field research cited below, units of 10 tons and under made up almost 60% of installed packaged DX capacity, and 5 tons was the most popular size. Efficiency is rated with EER (full-load efficiency at a standard condition) and IEER (integrated energy efficiency ratio, a weighted part-load metric). The U.S. Department of Energy has adopted new metrics for air-cooled commercial unitary equipment of 65,000 Btu/h and above: IVEC (Integrated Ventilation, Economizer and Cooling) and IVHE (Integrated Ventilation and Heating Efficiency), with compliance with the amended standards required on and after January 1, 2029 (DOE). For a sense of what efficient looks like today, ENERGY STAR's criteria for a small commercial unitary air conditioner (65,000 to 135,000 Btu/h, non-electric heat) are 12.5 EER and 17.8 IEER (ENERGY STAR). As of October 2026, ENERGY STAR is moving from EPA to DOE, with full transition planned by July 2027 (EPA), so check current criteria before relying on them for procurement or incentives.

How RTU efficiency degrades: what field studies found

A body of field research has examined RTUs as installed and operated. A 2004 ACEEE paper by Architectural Energy Corporation, the New Buildings Institute and the Consortium for Energy Efficiency summarized a three-year California Energy Commission study of newer small commercial rooftop units and similar studies elsewhere (ACEEE 2004):

ProblemWhat the studies found
Economizers64% total failure rate in the CEC study; other cited studies found 65% to 80%. Properly working economizers can provide 10% to 60% cooling energy savings depending on climate and building type.
Refrigerant charge46% of tested units failed a charge screening test, costing about 5% of annual cooling energy. A cited study of older units found 62% improperly charged, with an 11% cooling energy impact.
AirflowAbout 70% of units had 350 cfm per ton or less; the average was 325 cfm/ton against the roughly 400 cfm/ton on which ratings are generally based. Estimated impact: about 9% of annual cooling energy.
Fan power and static pressureAverage external static pressure of 0.48 inches of water column, versus 0.1 to 0.25 inches assumed in rating procedures.

These studies are now two decades old, and economizer controls have improved since, but the failure modes they describe (stuck dampers, drifting sensors, wrong setup, low airflow, wrong charge) are still what technicians find on roofs today. NIST's laboratory work on unitary equipment found that a 30% refrigerant undercharge, a level commonly seen in field surveys, reduced cooling efficiency by 7% to 15%, and a 30% airflow reduction cut efficiency by about 6%; the authors state that their results are representative of all unitary equipment including rooftop units (NIST TN 1848).

Beyond those installation and control faults, RTUs age in the same ways as other DX equipment:

  • Condenser coils on the roof collect dirt, cottonwood, grease from kitchen exhaust, and hail damage.
  • Evaporator coils load with dust when filters are missing, poorly fitted or overdue, and can grow biofilm in humid climates.
  • Belts and bearings slip and wear, lowering airflow.
  • Refrigerant-side oil. Some compressor oil circulates with the refrigerant and can accumulate on internal coil surfaces, adding resistance to heat transfer; see oil fouling and how coils transfer heat.
  • Controls: thermostats overridden, schedules lost after power outages, and minimum outdoor air set far higher than needed.

How to measure RTU efficiency in the field

You rarely get chiller-style kW/ton data for RTUs, but you can still build a useful picture.

  • Temperature split. The difference between return-air and supply-air temperature across the evaporator, with the economizer closed, at steady compressor operation. Compare with the manufacturer's expected range for the measured airflow and indoor humidity.
  • Superheat and subcooling against the manufacturer's charging chart, to verify charge.
  • Airflow measured with a flow grid or calculated from fan curves and static pressure, compared in cfm per ton.
  • Economizer functional test: command the dampers open and closed, verify sensor readings and changeover settings.
  • Compressor and fan amps at known outdoor conditions, trended over time.
  • Interval data. Many RTUs can be monitored with low-cost current transducers or a building automation system. Compressor run hours versus cooling degree days is a simple degradation indicator; see signs your HVAC is losing capacity.

Maintenance that matters

A typical RTU PM visit changes filters and belts. An efficiency-focused visit does more:

  1. Economizer: verify damper movement, linkage, actuator, sensors and changeover setpoints every season. A damper stuck wide open in summer adds load; one stuck closed loses free cooling.
  2. Airflow: check belt tension and sheave alignment, clean blower wheels, verify static pressure, and fix crushed or undersized ducts where possible.
  3. Coils: clean condenser and evaporator coils using methods appropriate to the coil construction.
  4. Charge: verify with superheat/subcooling rather than "topping off," and find leaks rather than refilling them.
  5. Controls: confirm schedules, setpoints and minimum outdoor air settings.

ASHRAE/ACCA Standard 180 sets minimum inspection and maintenance requirements for commercial HVAC intended to preserve comfort, energy efficiency and indoor air quality (ASHRAE/ACCA 180). Controls retrofits can be large, too: PNNL's field test of an advanced rooftop controller combining multi-speed fan control, integrated economizer control and demand-controlled ventilation reported 24% to 35% energy savings on RTUs with gas heat (PNNL).

Where an internal oil-film treatment fits

Once airflow, charge, economizers and coil cleanliness are right, the remaining heat transfer resistance is on the refrigerant side of the coils. CryogenX4 describes its treatment as removing insulating oil film from those internal surfaces and returning it to the compressor sump, conditioning the metal for better heat transfer, and improving the lubricity of the existing oil.

RTU fleets have a practical advantage for testing: you can treat a few identical units serving similar spaces and compare them to untreated units over the same weather, which gives a cleaner comparison than a single before-and-after test. CryogenX4 reports that installation is a one-time application done while the unit runs, usually in one day with no modifications. The company states energy savings of up to 30% and a typical treatment payback of 12 to 36 months; results vary by equipment condition.

Where it does not fit. An RTU with a failed economizer, low airflow or a leak will not be fixed by any refrigerant-side treatment. Fix those first; they are often cheaper and better documented. Units with failing compressors, severe coil corrosion, or a replacement scheduled within a year or two are better candidates for repair or replacement. See repair, retrofit or replace.

Questions to ask before treating rooftop units

  1. Has each candidate unit had an economizer functional test, airflow check and charge verification this season?
  2. Are the coils clean and in good condition?
  3. Which units run the most hours and serve the most critical spaces?
  4. Can we meter a treated group and an untreated control group of similar units? (See IPMVP options.)
  5. What is the age and expected remaining life of each unit?
  6. What does the manufacturer say about refrigerant-side treatments for these models, and what compatibility data does the provider supply?
  7. Would controls measures (scheduling, economizer repair, fan speed control) deliver savings faster? Compare in treatment vs VFDs and controls.

Next step

Pick your ten highest-run-hour RTUs, complete the five-point efficiency PM above, and log amps and temperature split. That list becomes the shortlist for a measured pilot.

Frequently asked questions

What is IEER and how is it different from EER?

EER is efficiency at a single full-load rating condition. IEER weights efficiency at several part-load points, which better reflects how RTUs actually run. DOE has adopted IVEC and IVHE as new metrics for larger commercial units, tied to amended standards with compliance from January 1, 2029.

How do I know if an RTU economizer is working?

Command it through its range and watch the dampers and actuator move, check that the outdoor-air and return-air sensors read correctly, and confirm the changeover setpoint suits your climate. Repeat each season; economizers fail silently.

Is it worth repairing an old RTU's economizer?

Often yes. Field research cited on this page found that properly working economizers can provide 10% to 60% cooling energy savings depending on climate and building type. In hot, humid climates the benefit is smaller, and a failed-open damper can add significant humidity load, so the repair is still important.

How many RTUs should be in a pilot?

Enough to compare against similar untreated units over the same weather. A few treated units matched with a few untreated units of the same model and use is a practical starting point; your M&V plan should define this before any work begins.

Sources

  1. Cooling commercial buildings is six times more energy-intensive in hot climates than cold (CBECS 2018) — U.S. Energy Information Administration
  2. Upstream Solutions to Downstream Problems: Improving Field Performance of Small Commercial Rooftop Units — ACEEE Summer Study 2004 (Architectural Energy Corp., New Buildings Institute, CEE)
  3. Sensitivity Analysis of Installation Faults on Heat Pump Performance (NIST Technical Note 1848) — National Institute of Standards and Technology
  4. Air-Cooled Unitary Air Conditioners and Heat Pumps (standards and test procedures) — U.S. Department of Energy
  5. Light Commercial HVAC Key Product Criteria — ENERGY STAR
  6. ENERGY STAR (program transition to DOE) — U.S. Environmental Protection Agency
  7. Advanced Rooftop Control (ARC) Retrofit: Field-Test Results — Pacific Northwest National Laboratory
  8. ASHRAE/ACCA Standard 180: Standard Practice for Inspection and Maintenance of Commercial Building HVAC Systems — ASHRAE / ACCA (listing via Standards Norway)

Keep reading

See what your equipment could save

CryogenX4 is a one-time treatment installed while your system runs. Start with a pilot on a few units, measured against a baseline, before you commit to a building or a portfolio.